Power |
|
|
|
Nominal Current |
|
16A to 630A per phase at 45°C |
|
Nominal Voltage |
|
200 V to 690 V |
|
Frequency |
|
Use from 47 to 63 Hz |
|
Dissipated Power |
|
1.3 W (approx.) per amp and
per phase |
|
Cooling |
|
Rating < 63 A: Natural
convection
Rating > 80 A: Fan-cooled
115 V or 230 V fan; consumption 10 VA |
|
Load |
|
Three-phase industrial load. |
|
Use category |
|
• AC-51 Resistive load with
low temperature coefficient.
• AC-55b Short wave infrared elements
• AC-56a Transformer primary and Resistive load with high temperature
coefficient. |
|
|
|
|
|
Control |
|
|
|
Supply |
|
Self-powered from supply network,
or external (115 V or 230 V +10%; -15%)
Consumption: 10 VA. |
|
Control type |
|
Analogue (optional digital communication)
• Remote analogue setpoint:
0-5 V or 0-10 V (100 kW . input),
0-20 mA or 4-20 mA (250 W input)
• Potentiometer for manual setpoint
(5 V supply available). |
|
|
|
|
|
Firing mode |
|
|
|
Firing at zero crossings |
|
• ‘Burst mode’
base time: 16 or 64 cycles
• ‘Single cycle’: base time 1 cycle
• ‘Advanced single-cycle’:
base firing time 1 cycle;
non firing by half-cycles. |
|
Firing angle variation |
|
• Phase angle |
|
|
|
|
|
Control |
|
|
|
Control parameter |
|
• Standard:
- load voltage squared (V2)
• Option:
- - apparent power (V × I)
- - load current squared (I2)
- - open loop. |
|
Linearity and Stability |
|
Better than ±2% of full
scale
(balanced supply and load). |
|
Current limit |
|
Option, depending on firing
mode:
• ‘Phase angle’:
Automatic control transfer
- from V2 to I2 or
- from V × I to I2
with current recalibration set by potentiometer on front panel.
• Burst mode, 16 cycle base:
Current limited by threshold set using potentiometer on front panel. |
|
Calibration |
|
A control signal is available
in V × I for power and current calibration and maintenance. |
|
Transient current
limit |
|
Option for transformer primary
control in ‘burst mode’ firing:
• Transformer magnetisation firing angle ramp at first switch on.
• First firing delay adjustable using potentiometer on front panel. |
|
|
|
|
|
Signalling |
|
Electronics supply present:
green ‘ON’ LED.
Thyristor firing request:
green ‘HEAT’ LED. |
|
|
|
|
|
Type 1 alarms (Options) |
|
|
|
Serious alarms |
|
Total load failure and thyristor
short |
|
(GRF option) |
|
circuit detection.
Signalled by red ‘GRF’ LED and alarm relay contact. |
|
Diagnostic alarm |
|
Partial load failure detection. |
|
(DLF option) |
|
Signalled by orange ‘DLF’ LED
and alarm relay contact.
Settings: Monitoring diagnosis, alarm adjustment and resetting using
push button on front panel.
Sensitivity: Detects the failure of at least one heating element for
six identical elements connected in parallel.
The DLF option includes serious alarm monitoring (GRF). |
|
Over-temperature
alarm |
|
For all fan-cooled units (>
80 A) operation stops if the temperature threshold is exceeded.
Signalled by red ‘T°’ LED and alarm relay (if GRF or DLF option
selected). |
|
|
|
|
|
Type 2 alarm (Option) |
|
|
|
Over-current alarm |
|
Operation stopped if current
threshold |
|
(ICO option) |
|
exceeded.
Only available with zero crossing firing and DLF option (except for
short wave infrared elements, transformers and codes VICL and V2CL).
Alarm threshold adjustable from 20 to 100% using potentiometer on front
panel.
Signalled by red ‘ICO’ LED and alarm relay contact. |
|
|
|
|
|
Alarm relay |
|
Available with alarm options.
The relay contact (0.25 A/230 Vac; 32Vdc) is either open on alarm or
closed on alarm depending on the product code. |
|
|
|
|
|
Communication |
|
Available later. |
|
|
|
|
|
Protection |
|
|
|
Thyristor protection |
|
Varistor and RC snubber.
Short circuit Coordination type : Type 1.
High speed fuses :
. rating < 100 A: external (optional)
. rating > 125 A: internal.
No fuse for short wave infrared elements in firing at zero crossings
or in phase angle firing mode without current limit. |
|
Electrical protection |
|
IP20 without adding additional
protection.
Overvoltage category 3 (defined by IEC 664). |
|
|
|
|
|
Product standard |
|
The 7300A products comply with
the terms of product standard EN 60947-4-3
‘Contactors and motor-starters -
AC semiconductor controllers and contactors for non-motor loads’. |
|
|
|
|
|
CE labelling |
|
Complies with the essential
requirements of the European Low Voltage Directive 73/23 EEC dated 19 February
1973, modified by 93/68/EEC dated 22 July 1993 and the Electromagnetic
Compatibility Directive 89/336/EEC dated 3 May 1989 modified by 92/31/EEC
dated 28 April 1992 and 93/68/EEC dated 22/07/93. |
|
|
|
|
|
Environment |
|
|
|
Use |
|
0 to 45°C with nominal current,
at max. altitude of 2000 m. |
|
Storage |
|
-10°C to 70°C. |
|
Pollution |
|
Degree 2 acceptable (defined
by CEI 664). |
|
Humidity |
|
RH 5% to 95% non-condensing. |
|
|
|
|
|
Dimensions |
|
Rating 16 A to 40 A: |
|
H × W ×
D (overall) |
|
Basic version: 220 × 96
× 215 mm
Options: 220 × 96 × 243 mm. |
|
Weight |
|
Maximum 2.5 kg. |