Power |
|
|
|
Nominal
Current |
|
16A,
25A, 40A, 63A, 100A, 125A, 160A, 200A and 250A |
|
Nominal
Voltage |
|
127Vac,
230Vac, 277Vac, 500V or 690Vac |
|
Frequency |
|
47
to 63 Hz |
|
Dissipated
Power |
|
Approximately
2W per Amp including heat dissipation from external fuse if used. |
|
Cooling |
|
Natural
convection |
|
Load |
|
Single
phase industrial load.
Resistive loads with low
temperature coefficient or Short-Wave Infrared heaters. |
|
Power
Supply |
|
No
Auxillary supply is required - an internal, synchronized electronic supply
is internal |
|
|
|
|
|
Thyristor
Firing Mode |
|
|
|
Logic
Inputs |
|
For
logic inputs ON/OFF with zero-voltage switching.
If input from a REMIO unit
and depending on the REMIO operating mode either:
· 8-cycle burst mode
or
· intelligent half-cycle |
|
4-20mA
Input |
|
The
firing mode is Fast Cycle. Power modulation as a function of the signal.
At 50% of input signal, the modulation period is 0.6s with 0.3s firing.
Linearity better than +- 2% of full scale. |
|
Control |
|
Open
Loop |
|
|
|
|
|
Input |
|
|
|
DC
Logic (LDC) |
|
Conducting
from 4.5Vdc to 32Vdc Maximum;
On > 4.5Vdc, Off < 2Vdc;
On >= 9mA, Off < 0.5mA. |
|
AC
Logic (HAC) |
|
Conducting
from 85Vac to 253Vac Maximum;
On > 85Vac, Off <10Vac;
Impedance 7Kohms at 50Hz. |
|
DC
Analog (ATP) |
|
4-20mA.
Voltage 10Vdc Maximum. |
|
|
|
|
|
Environment |
|
|
|
Usage |
|
0
to 45 degC at a maximum altitude of 2000m |
|
Storage |
|
-10
deg C to 70 degC |
|
Pollution |
|
Degree
2 Allowable (Defined by IEC 664) |
|
Humidity |
|
RH
5% to 95% non-condensing, non-streaming |
|
Protection |
|
IP20
without additional protection. Overvoltage category 3. |
|
Thyristor
Protection |
|
High-Speed
external fuse (i2t) |
|
|
|
|
|
Indication |
|
|
|
|
|
Mains
Supply: Green ON LED |
|
|
|
Thyristor
Firing: Green HEAT LED |
|
|
|
|
|
Alarm
Options |
|
|
|
GRF |
|
Gross
Fault, detects a shorted device and an open load |
|
DLF |
|
Diagnostic
Load Failure, detects a shorted device, an open load and partial load failure |
|
|
|
|
|
Communication
Options |
|
|
|
|
|
Modbus
RTU @ 9K6 or 19K2 Baud |
|
|
|
|
|
Installation |
|
|
|
Mounting |
|
Panel
or symmetrical Din Rail |
|
Cable
Size |
|
16A
and 25A: 6mm2
40A and 63A: 16mm2
80A and 100A: 35mm2
125A, 160A and 200A: 120mm2
250A: 120mm2 |
|
|
|
|
|
Dimensions
(mm) |
|
|
|
16A |
|
156H
x 35W x 110D, 0.42Kg |
|
25A |
|
156H
x 35W x 140D, 0.56Kg |
|
40A |
|
156H
x 52.5W x 140D, 0.8 Kg |
|
63A |
|
156H
x 70W x 160D, 1.3 Kg |
|
80-100A |
|
226H
x 96W x 164D, 1.7 Kg |
|
125-200A
|
|
424H x 144W
x 285D, 5.1 Kg |
|
250A
|
|
424H x 144W
x 285D, 5.6 Kg |