Features
  • 16-250 amps, 120-600Vac 
  • On-Off Logic or Fast Cycle Firing 
  • Suitable for SWIR or Resistive Loads 
  • Load Diagnostics and Fault Indication 
  • Optional Modbus® RTU Comms
  • Fixed build design 
  • Zero cross fired 
  • LED status indicator 
  • The Model 7100S is a new range of economic solid state contactors for use with low temperature coefficient resistive loads. This unit features integral heatsinks with AC or DC logic inputs for fast switching that reduces thermal cycling of the heating elements resulting in longer element life. Options include Gross Fault (GRF) and Diagnostic Load Failure (DLF).  GRF indicates when a shorted device or an open load is detected. Similar to GRF, DLF detects a shorted device, an open load and partial load failure. There are no mechanical contacts to wear out and so maintenance costs and downtime are reduced. Silent operation and lack of electrical interference achieved by zero voltage switching give environmentally friendly operation. 

    TECHNICAL SPECIFICATIONS

    Power
    Nominal Current 16A, 25A, 40A, 63A, 100A, 125A, 160A, 200A and 250A
    Nominal Voltage 127Vac, 230Vac, 277Vac, 500V or 690Vac
    Frequency 47 to 63 Hz
    Dissipated Power  Approximately 2W per Amp including heat dissipation from external fuse if used.
    Cooling Natural convection
    Load Single phase industrial load.
    Resistive loads with low temperature coefficient or Short-Wave Infrared heaters.
    Power Supply No Auxillary supply is required - an internal, synchronized electronic supply is internal
     
    Thyristor Firing Mode
    Logic Inputs For logic inputs ON/OFF with zero-voltage switching. 
    If input from a REMIO unit and depending on the REMIO operating mode either:
    · 8-cycle burst mode or
    · intelligent half-cycle
    4-20mA Input The firing mode is Fast Cycle. Power modulation as a function of the signal. At 50% of input signal, the modulation period is 0.6s with 0.3s firing. Linearity better than +- 2% of full scale.
    Control Open Loop
     
    Input    
    DC Logic (LDC) Conducting from 4.5Vdc to 32Vdc Maximum;
    On > 4.5Vdc, Off < 2Vdc; On >= 9mA, Off < 0.5mA.
    AC Logic (HAC) Conducting from 85Vac to 253Vac Maximum;
    On > 85Vac, Off <10Vac; Impedance 7Kohms at 50Hz.
    DC Analog (ATP) 4-20mA. Voltage 10Vdc Maximum.
     
    Environment
    Usage 0 to 45 degC at a maximum altitude of 2000m 
    Storage -10 deg C to 70 degC
    Pollution Degree 2 Allowable (Defined by IEC 664)
    Humidity RH 5% to 95% non-condensing, non-streaming
    Protection IP20 without additional protection. Overvoltage category 3.
    Thyristor Protection High-Speed external fuse (i2t)
     
    Indication
    Mains Supply: Green ON LED
    Thyristor Firing: Green HEAT LED
     
    Alarm Options
    GRF Gross Fault, detects a shorted device and an open load
    DLF Diagnostic Load Failure, detects a shorted device, an open load and partial load failure
     
    Communication Options
    Modbus RTU @ 9K6 or 19K2 Baud
     
    Installation
    Mounting Panel or symmetrical Din Rail
    Cable Size 16A and 25A: 6mm2
    40A and 63A: 16mm2
    80A and 100A: 35mm2
    125A, 160A and 200A: 120mm2
    250A: 120mm2
       
    Dimensions (mm)
    16A 156H x 35W x 110D,    0.42Kg
    25A 156H x 35W x 140D,   0.56Kg
    40A 156H x 52.5W x 140D,   0.8 Kg
    63A 156H x 70W x 160D,   1.3 Kg
    80-100A 226H x 96W x 164D,   1.7 Kg
    125-200A
    424H x 144W x 285D,   5.1 Kg
    250A
    424H x 144W x 285D,   5.6 Kg