Power |
|
|
|
Nominal
Current |
|
16A, 25A,
40A, 63A and 100A |
|
Nominal
Voltage |
|
230Vac (48-264Vac),
500Vac (96-550V), 600Vac (96-660V (Non CE)) |
|
Frequency |
|
47 to 63
Hz |
|
Dissipated
Power |
|
Approximately
1.3W per Amp. Allow 2W per Amp to include heat dissipation from fuse if
used. |
|
Cooling |
|
Natural
convection |
|
Load |
|
Constant
resistance single phase industrial load, switched Line to Neutral or Line
to Line. |
|
|
|
|
|
Thyristor
Firing Mode |
|
|
|
Logic Inputs |
|
For logic
inputs ON/OFF with zero-voltage switching. |
|
Control |
|
Open Loop |
|
|
|
|
|
Input |
|
|
|
DC
Logic (LDC) |
|
Conducting
from 4.5Vdc to 32Vdc Maximum;
On > 4.5Vdc, Off < 2Vdc; On >=
9mA, Off < 0.5mA. |
|
AC
Logic (HAC) |
|
Conducting
from 85Vac to 253Vac Maximum;
On > 85Vac, Off <10Vac; Impedance
7Kohms at 50Hz. |
|
|
|
|
|
Environment |
|
|
|
Usage |
|
0 to 45
degC at a maximum altitude of 2000m |
|
Storage |
|
-10 deg
C to 70 degC |
|
Pollution |
|
Degree 2
Allowable (Defined by IEC 664) |
|
Humidity |
|
RH 5% to
95% non-condensing, non-streaming |
|
Protection |
|
IP20 without
additional protection. Overvoltage category 3. |
|
Thyristor
Protection |
|
High-Speed
external fuse (i2t) |
|
|
|
|
|
Indication |
|
|
|
|
|
Green HEAT
LED on front face indictes presence of input signal. |
|
|
|
|
|
Installation |
|
|
|
Mounting |
|
Panel or
symmetrical Din Rail |
|
Cable
Size |
|
16A and
25A: 6mm2
40A and 63A: 16mm2
80A and 100A: 35mm2 |
|
|
|
|
|
Dimensions
(mm) |
|
|
|
16A |
|
156H x 35W
x 110D |
|
25A |
|
156H x 35W
x 140D |
|
40A |
|
156H x 52.5W
x 140D |
|
63A |
|
156H x 70W
x 160D |
|
80-100A |
|
226H x 96W
x 164D |