Features
LED status indicator
16-100 amps, 120-500Vac
Zero cross or phase angle firing
Optional current limit
Optional Modbus® RTU Comms
|
|
| The Model 7100A is a new range of
economic SCR Power Controllers for use with resistive, infrared or inductive
loads. This unit features integral heatsinks with analog voltage or current
inputs for precise control. Options include Gross Fault (GRF) Detection,
Diagnostic Load Failure (DLF) Detection, Current Limit and digital communications. |
GRF indicates when a shorted device
or an open load is detected. Similar to GRF, DLF detects a shorted device,
an open load and partial load failure. Current limit is available for use
with variable resistance loads and digital communications is available
for remote control or monitoring of the process. |
|
TECHNICAL SPECIFICATIONS
 |
|
Line Voltage: |
100V - 500V (+10%, -15%),
47-63 Hz |
| Load: |
Resistive, short wave
infrared, inductive/transformer coupled |
| Firing Mode: |
Fast Cycle, Single Cycle,
Advanced Single Cycle or Phase Angle |
| Inputs: |
DC current: |
0-20mA or 4-20mA |
|
DC voltage: |
0-5V or 0-10V |
|
Potentiometer: |
10kž external, customer
supplied |
| Comms: |
Modbus® |
9600 or 19200 baud |
| Ambient: |
|
0-45°C |
| Options: |
GRF |
Gross Fault, detects
a shorted device and an open load |
|
DLF |
Diagnostic Load Failure,
detects a shorted device, an open load and partial load failure |
|
CL |
Current limit (phase
angle only) |
| Mounting: |
|
Panel or symmetrical
Din Rail |
| Dimensions (mm) |
16A |
156H x 35W x 110D |
|
25A |
156H x 35W x 140D |
|
40A |
156H x 52.5W x 140D |
|
63A |
156H x 70W x 160D |
|
80-100A |
226H x 96W x 164D |
|
|
|