Eurotherm
Invensys
.

Multi-channel Loop-powered Isolator - Q500

Shop Online

The ActionI/Q model Q500 is a DIN rail mount, loop-powered isolator, with single, dual or quad (4) channel capability. Each channel accepts a 0-20mA or 4-20mA input, provides up to 1800VDC of isolation and outputs a proportional 0(4)-20mA signal. The Q500 provides signal isolation from input to output and channel to channel.

 

All ActionI/Q modules feature SnapLoc, plug-in, screw terminals for easy installation and low Mean-Time- To-Repair (MTTR). If desired, two or more modules can slide together and interlock for solid, high density mounting. This is accomplished by removing either the foot, or the adjacent unit's face plate, for right-hand side or left-hand side mounting, respectively. The module to be attached will easily slide on to the side of the mounted unit.

Application

Loop-powered isolators are used to isolate process signals transmitted between field instrumentation, Programmable Logic Controllers (PLC), Distributed Control Systems (DCS) and Data Acquisition Systems (DAS). Outputs from these systems can also drive one or more isolator channels of the Q500. Field devices such as flow, level or temperature transmitters may also drive a Q500 isolator channel.

 

The 1800VDC isolation capability of the Q500 prevents ground loops from causing errors in 4-20mA current signals and may reduce susceptibility to Radio Frequency Interference (RFI). Isolation also provides protection from high voltages and current spikes which may damage expensive Supervisory Control And Data Acquisition (SCADA) equipment, such as a PLC or DCS.

Operation

The ActionI/Q model Q500 operates as a looppowered isolator, with each channel deriving its power from the input loop current, 0(4)- 20mA. The effective load of a Q500 isolator channel on a loop is 300W plus the output load resistance. For example, if the load on an output of the Q500 is 500W, then the current loop connected to the input of the Q500 would need to drive 300W plus 500W (i.e. 800W) at a maximum current of 20mA, or 800W x 20mA which equals 16.0V.

Q500

FEATURES:

  • Multi-Channel Design Provides One (1), Two(2) or Four(4) Loop Isolators in a Single Package

  • High Density DIN Rail Mounting

  • SnapLoc, Plug-In, Screw Terminals for Low MTTR

  • Input Loop-Powered Design Provides up to 500. Output Drive (10V)

  • Prevents Ground Loops and Protects Equipment with up to 1800V Isolation

  • Three Year Warranty

The Q500 is protected from reverse input polarity and output short circuit. A span pot is provided for each channel to calibrate the output to the load.

Calibration
  1. Connect the input to a calibrated milliamp source. Connect the output to the actual device load or to a load (between 100 and 500W) equivalent to the actual device load value. Monitor the output current with a milliamp meter in series with the load or monitor the voltage across the load.
  2. Set the calibrator to 20mA and adjust the span potentiometer for 20mA output.
  3. Set the calibrator to 4mA and confirm that the output is 4mA.
TECHNICAL SPECIFICATION (Q500)  

Input 

  • Ranges: 0(4) to 20mA, 30VDC max, each channel 
  • Voltage Drop: 6V (300W), plus output load

Output 

  • Range: 0 (4) to 20mA, 
  • Drive: 10V or 500W maximum @ 20mA, 100W minimum

Output Accuracy   

Better than ± 0.2% of full-scale, including linearity, repeatability, maximum

 

Linearity     

0.1% of span typical, from 4 to 20mA at 250W load

 

Stability     

±0.02%/oC of span maximum for full-scale and zero

 

Load Regulation     

±0.1% of span, typical per 10W change

 

Common Mode Rejection Ratio   

> 100dB (DC to 60Hz)

 

Isolation     

1800V DC, input to output and channel to channel.

 

ESD Susceptibility   

Capable of meeting IEC 801-2 level 3 (8kV)
Response Time     

50mSec typical, 100mSec max 10 to 90% (each channel)

Temperature 

  • Operating: -40 to 80oC (-40 to 176oF) 
  • Storage: -40 to 80oC (-40 to 176oF)

Humidity (non-condensing)   

25 to 95% (@40oC)

Wire Terminal     

Socketed screw terminals for 12-22 AWG

Weight     

0.34lbs

Agency Approvals   

  • CSA certified per standard C22.2 (File No. LR42272).
  • UL recognized per standard UL508 (File No.E99775).
  • CE conformance per EMC directive 89/336/EEC and Low voltage 73/23/EEC.
Ordering Information
1. Specify: (model number)   Q500-1B00, Single (1) Channel Loop-Powered Isolator,
      Q500-2B00, Dual (2) Channel Loop- Powered Isolator
      Q500-4B00, Quad (4) Channel Loop-Powered Isolator
2. Accessories: (see Accessories)
Accessories
All ActionI/Q modules mount on standard TS32 (model MD02) or TS35 (model MD03) DIN rail. In addition the following accessories are available:
  MD02   TS32 DIN rail
  MD03   TS35 x 7.5 DIN rail
  G905   24VDC Power Supply (500mA)
  H902   24VDC Power Supply (200mA)
  H910   24VDC Power Supply (1 Amp)
  H915   24VDC Power Supply (2.3 Amp)

Get a Quote

» Indicates required fields

Request for Quote
Your Details
Company Details
*Leave State / Province Code  blank if not applicable*
Contact Details
Product Requirements

Get Support

Visit the Eurotherm Support site